Poll S7-300, S7-400, S7-1200 and S7-1500 controllers (PUT/GET, non-optimised DBs) with an address map.
Siemens S7 (S7-300, 400, 1200, 1500)
Siemens S7-300, S7-400, S7-1200 and S7-1500 controllers (and the S7-1500 software controller) answer the classic S7 protocol on TCP port 102. The collector polls the addresses you list in a map and publishes every poll as a sample. It only reads. S7-1200 and S7-1500 CPUs refuse this protocol until you allow it in TIA Portal (next section).
Prepare the PLC (S7-1200 and S7-1500)
- In TIA Portal open the CPU properties, Protection & Security, Connection mechanisms, and tick Permit access with PUT/GET communication from remote partner. Without it every read is refused.
- For every data block you want to read, open its properties, Attributes, and clear Optimized block access; then compile and download (otherwise the PLC answers "object does not exist"). After clearing the box the offsets are shown in the DB's Offset column: those are the numbers for the
bytecolumn. Merkers (M), inputs (I), outputs (Q), timers and counters need nothing special. - Apply a CPU access level that still lets this read through (full access or read access without a password prompt on the PUT/GET connection).
Configuration
streams:
- name: Packaging line PLC
mode: live # live | record (also kept in the cloud)
sources:
- name: Packaging line PLC
type: s7
host: 10.20.0.30
cpu: s7-1500 # sets rack 0 / slot 1; s7-300 is 0/2, s7-400 is 0/3
poll_ms: 500
map: s7.csv| Name | Type | Description |
|---|---|---|
hostrequired | string | The CPU’s address (its PROFINET/Ethernet port, or a CP). |
port | numberDefault: 102 | ISO-on-TCP port. |
cpu | s7-300 | s7-400 | s7-1200 | s7-1500Default: s7-1500 | Picks the default rack and slot: 0/2 for S7-300, 0/3 for S7-400, 0/1 for S7-1200 and S7-1500. |
rack, slot | numberDefault: from cpu | Override when the CPU sits elsewhere (an S7-400 in a multi-rack setup, a CPU behind a CP). Wrong values give a connection error. |
maprequired | path | list | The address map: a CSV relative to collector.yaml, or its rows written right here (see below). |
poll_ms | numberDefault: 1000 | Default poll interval; a row can set its own. |
timeout_s | numberDefault: 3.0 | Per request. A request that fails or times out turns its tags into gaps and the collector reconnects; an offline PLC never delays other sources. |
max_gap | numberDefault: 8 | Bytes that may be read and thrown away to merge two nearby tags of the same DB into one request. 0 merges only touching tags. |
The address map
One row per tag. Column order does not matter; name, area, byte and type are required.
name,area,db,byte,bit,type,scale,offset,unit,poll_ms,description
Line speed,DB,10,0,,REAL,,,m/min,,
Tank level,DB,10,4,,INT,0.1,,%,1000,Raw is tenths of a percent
Batch count,DB,10,6,,DINT,,,,,
Motor running,DB,10,10,0,BOOL,,,,,Bit 0 of byte 10
Door open,M,,20,3,BOOL,,,,,
Start button,I,,0,1,BOOL,,,,,
Valve 1 command,Q,,4,0,BOOL,,,,,
Cycle timer,DB,10,12,,S5TIME,,,s,,
Timer T5,T,,5,,S5TIME,,,s,,Timer number in the byte column
Parts counter C2,C,,2,,UINT,,,,,Counter number in the byte column
Last cycle,DB,10,16,,TIME,0.001,,s,,TIME is milliseconds
Batch start,DB,10,20,,DATE_AND_TIME,,,,,Unix seconds (UTC)| Name | Type | Description |
|---|---|---|
namerequired | string | The channel name in Kymoscope. Unique within the source. |
arearequired | DB | M | I | Q | T | C | Data block, merkers, inputs, outputs, timers, counters. |
db | number | The DB number (area DB only). |
byterequired | number | Byte offset in the DB or area (0x hex accepted). For T and C it is the timer or counter number. |
bit | number 0-7 | The bit inside the byte, required for BOOL (DBX10.3 is byte 10, bit 3). |
typerequired | BOOL BYTE WORD DWORD INT DINT UINT UDINT LINT REAL LREAL S5TIME TIME DATE DATE_AND_TIME | S7 types are big-endian. INT is 16-bit signed, DINT 32-bit signed, REAL a 32-bit float, LREAL 64-bit. S5TIME is read as seconds. TIME is milliseconds (scale 0.001 for seconds). DATE and DATE_AND_TIME are Unix seconds (DATE_AND_TIME is taken as UTC). Timers are S5TIME and counters UINT. |
scale, offset | numberDefault: 1, 0 | value = raw x scale + offset. |
unit | string | Engineering unit shown on the channel. |
poll_ms | number | This tag’s interval; tags of the same area, DB and interval are read together. |
description | string | Free text. |
The same rows can live in collector.yaml itself, with the same column names, so the whole source is one file:
streams:
- name: Packaging line PLC
mode: live # live | record (also kept in the cloud)
sources:
- name: Packaging line PLC
type: s7
host: 10.20.0.30
cpu: s7-1500
map:
- {name: Line speed, area: DB, db: 10, byte: 0, type: REAL, unit: m/min}
- {name: Motor running, area: DB, db: 10, byte: 10, bit: 0, type: BOOL}Nearby tags are read together, so a map of hundreds of tags costs a handful of requests per poll. Strings, arrays and structures are not read as such: list the elements you need one by one.
Gaps, errors and health
- Every sample is stamped with the time the response arrived.
- When the connection drops or a request times out, the tags of that poll are stored as gaps (Bad status), never as the last value. The collector reconnects on its own.
- When the PLC refuses an address, only that tag becomes a gap. The log names the tag once with the likely cause: access refused (PUT/GET not permitted or a CPU password), object does not exist (the DB is missing or still optimised) or invalid address(offset past the end of the DB).
connected, reconnects, polls, poll_errors, overruns, last_poll_s, values_per_s,
refused_03 (access refused), refused_05 (invalid address), refused_0a (object does not exist) ...discover and backfill
discover writes the tags of the map as a tags file; the classic protocol cannot list a PLC's variables. backfill does not apply: an S7 CPU keeps no history, so a gap while the collector is down stays a gap (the collector's disk buffer covers outages of the link to Kymoscope).
Permissions the collector needs
- TCP port 102 from the collector host to the CPU, and the PUT/GET setting above for S7-1200 and S7-1500. The collector only reads; it never writes to or controls the PLC.
- The classic S7 protocol has no encryption. Keep it on your internal network; the data leaves your site encrypted. Many CPUs allow only a few simultaneous PUT/GET connections (S7-1200: 3 to 8 depending on firmware): the collector uses one.
- Install with
pip install "kymoscope-collector[s7]"(pure Python, no Siemens software needed).